What is a Unity Pro / Control Expert .DTX file?
From the Control Expert menu:  PLC - Save/Restore data between a file and the PLC

Data Transfer allows you to store the value of the following data in a file that can be downloaded to or uploaded from a PLC.
%M
%MW
unlocated variables
function block instances

Restoring data from a .DTX file is allowed even if the application has been built and/or data has been modified since 'Save Data from LC to  File' was performed.
(This is not possible if the data has been saved to a .DAT file.  For this reason, we recommend saving to a .DTX file).

In order to 'Save Data from PLC to File', the following must be true:
- PLC has a project loaded.
- PLC is in RUN or STOP mode.
- Unity Pro is running and connected to the PLC
- The project is built and is EQUAL to the PLC.

In order to 'Restore Data from File to PLC, point to the .DTX file that was previously saved.

NOTE:  I/O and Device DDT objects cannot be saved in.DTX files.
SFC variables cannot be restored.

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.