{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What would cause the ATV66 drives to blow the input line fuses on power up?

Issue:
Possible causes for an ATV66 drives to blow the input line fuses on power up.

Product Line:
Altivar ATV66

Environment:
All

Cause:
Internal short inside the drive.

Resolution:
Before replacing the line fuses and power it back up again, please get a Fluke meter, and do a full diode static check on the input L1 L2 L3 and  U, V, W output terminals to + and - bus.
The full diode check will show you two readings, you will measure .3vdc to .7vdc in forward bias direction or OL in the reverse direction.
Please reference the ATV66 troubleshooting and repair manuals VD0C06S701, and VD0C06S702 for more information on where and how do perform static checks on the drive.

DRIVES

Schneider Electric India

Explore more
Range:
MRCA/MRWA Mount - Legacy
Explore more
Range:
MRCA/MRWA Mount - Legacy
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.