{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What does it meant "Uct = 36 KV DC" on rating plate of Premset (Cable testing and cable diagnosis option).

This is a new rating, introduced in the latest edition of IEC 62271-200, regarding the ability of a disconnecting device to withstand the cable test voltage on one side and the network voltage on the other side. By the way, it gives also the maximum rating of applicable cable test voltage (Uct, ct stands for "cable test").

Schneider Electric India

Explore more
Range:
SM6-36
Explore more
Range:
SM6-36
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.