Why does F010 fault occurs in ATV310 Drive
Name of fault :- Over current

Possible causes:-

• Parameters in the Motor control menu are not correct
• Inertia or load too high
• Mechanical locking

Remedy :-

• Check the motor control parameters.
• Check the size of the motor/drive/load.
• Check the state of the mechanism.
• Connect line motor chokes.
• Reduce the Switching frequency range
• Check the ground connection of drive, motor cable and motor insulation.