{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Where do you wire in remote speed reference to an ATV660?

Issue:
Wiring remote speed reference for an ATV660.

Product Line:
ATV660

Environment:
ALL

Cause:
Wiring / Programming

Resolution:
Customer Contacts for external analog input control signal.
TB1-11 = COM / Neutral
TB1-12 = AI3 Signal wire (programmable for 0-10, factory set for 4-20ma)
Program under :  Complete Settings > Inputs/Outputs > AI/AQ tab > AI3 Configuration

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: