Video: How to clear run hours violation on Uniflair Chilled Water Heater Elements
Issue:
How to clear Heater Run Hours Violation.
Product line:
Uniflair: TDCV700X, TDCV1000X, TDCV1200X, TDCV1700X, TDCV2500X, TDCV3400X, TDCV4000X, TDCV4300X, TUCV700X, TUCV1000X, TUCV1200X, TUCV1700X, TUCV2500X, TUCV3400X, TUCV4000X, TUCV4300X, HDCV4500X, HDCV5000X.
Environment:
All Serial Numbers
Cause:
Install, Repair
Resolution
Press PRG
Use the DOWN arrow to scroll to Hourmeter Settings.
Press ENTER.
Use the DOWN arrow to scroll to Heater 1 Run Hours.
Press ENTER twice.
Press the DOWN arrow once.
Press ENTER again to clear run hours.
Press ESC three times to exit back to main menu.
How to clear Heater Run Hours Violation.
Product line:
Uniflair: TDCV700X, TDCV1000X, TDCV1200X, TDCV1700X, TDCV2500X, TDCV3400X, TDCV4000X, TDCV4300X, TUCV700X, TUCV1000X, TUCV1200X, TUCV1700X, TUCV2500X, TUCV3400X, TUCV4000X, TUCV4300X, HDCV4500X, HDCV5000X.
Environment:
All Serial Numbers
Cause:
Install, Repair
Resolution
Press PRG
Use the DOWN arrow to scroll to Hourmeter Settings.
Press ENTER.
Use the DOWN arrow to scroll to Heater 1 Run Hours.
Press ENTER twice.
Press the DOWN arrow once.
Press ENTER again to clear run hours.
Press ESC three times to exit back to main menu.