{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Video: How to clear run hours violation on Uniflair Chilled Water Heater Elements

Issue:
How to clear Heater Run Hours Violation.

Product line:
Uniflair: TDCV700X, TDCV1000X, TDCV1200X, TDCV1700X, TDCV2500X, TDCV3400X, TDCV4000X, TDCV4300X, TUCV700X, TUCV1000X, TUCV1200X, TUCV1700X, TUCV2500X, TUCV3400X, TUCV4000X, TUCV4300X, HDCV4500X, HDCV5000X.

Environment:
All Serial Numbers

Cause:
Install, Repair

Resolution

Press PRG

Use the DOWN arrow to scroll to Hourmeter Settings.

Press ENTER.

Use the DOWN arrow to scroll to Heater 1 Run Hours.

Press ENTER twice.

Press the DOWN arrow once.

Press ENTER again to clear run hours.

Press ESC three times to exit back to main menu.

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: