Video: How to clear run hours violation on Uniflair Chilled Water Heater Elements

Issue:
How to clear Heater Run Hours Violation.

Product line:
Uniflair: TDCV700X, TDCV1000X, TDCV1200X, TDCV1700X, TDCV2500X, TDCV3400X, TDCV4000X, TDCV4300X, TUCV700X, TUCV1000X, TUCV1200X, TUCV1700X, TUCV2500X, TUCV3400X, TUCV4000X, TUCV4300X, HDCV4500X, HDCV5000X.

Environment:
All Serial Numbers

Cause:
Install, Repair

Resolution

Press PRG

Use the DOWN arrow to scroll to Hourmeter Settings.

Press ENTER.

Use the DOWN arrow to scroll to Heater 1 Run Hours.

Press ENTER twice.

Press the DOWN arrow once.

Press ENTER again to clear run hours.

Press ESC three times to exit back to main menu.