{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

How the Watchdog relay of P122 works.

The watchdog output is changeover contact, NO will become NC after powering up & healthy
The normally closed (NC) contact of the Watchdog (RL0) cannot be configured.

In power Off condition 35-36 is closed; 36-37 is open.
Once the relay is powered up, the RL0 relay is energized i.e. 36-37 is closed; 35-36 is Open & this is a healthy condition.

Major fault:
The protection and automation functions are stopped.
The RL0 watchdog relay is de-energized (35-36 contact closed).

Minor fault:
The MiCOM relay is fully operational.
The RL0 watchdog relay is energized (35-36 contact open, 36-37 contact closed).

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: