What is a Ot fault on a ATV212 drive?

Issue:

Getting Ot fault on a ATV212 drive

Product Line:

ATV212

Environment:

Ot faults

Cause:

n/a

Resolution:

This is a Overtorque fault. The calculated motor torque has reached the level set by Parameter F616 (Overtorque Detection Level)- factory default set to 130%, can increase, if needed.
F615 (Overtorque fault/alarm selection)- can set to 0 for Alarm or 1 for Fault.