{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What is First pole-to-clear factor for medium voltage breaker

For three-phase circuits, the TRV (Rated Transient Recovery Voltage) refers to the pole that breaks the circuit initially, in other words the voltage across the terminals of the first open pole. The ratio of this voltage to a single phase circuit voltage is called the first pole-to-clear factor, it is equal to 1.5 for voltages up to 72.5 kV
(isolated neutral of the supply circuit).

Schneider Electric India

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: