Can we set the SDV earth leakage fault indication for Micrologic 4 in latch mode using the communication network or the Micrologic keypad?

For Micrologic 4, the SDV earth leakage fault indication will return automatically to their initial state
when the circuit breaker closes. Latching mode can’t be selected as there is no communication function in this trip unit.
In the case of Micrologic 4 AL, the breaker does not trip even if an electric leakage occurs.
You can reset the earth leakage display by pressing the test button for 5 seconds.