{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How to troubleshoot CANOpen communication using BMECXM module with M580? For example, ATV process with BMECXM module.
Refer the below steps.
  1. Security is the main reason. Unlock the Security under DTM configuration. Open Control expert, select processor. Double click on security and unlock the securities. Double Click on BMECXM module, click on service configuration tool which is available in Advance Configuration. Click on security tap and click on unlock security. Click on apply and save. Refer the below screen shot for more details.Ist
  2. Set the transmission speed of BMECXM which should be same as in ATV930. Refer the below screen shot.sec
  3. Open the CanOpen bus and check the node address parameter which should be the same with derive.third
  4. Check the DTM which should be compatible the firmware with drive(device).
  5. Rebuild the program and transfer to PLC.
  6. Verify the wiring details as per below.forth
  7. Open the DDT variable in animation table of Control Expert and check the can health bit. Refer the below snapshot.fifth
Note: We recommend using shield cable for communication of ATV930 with BMECXM0100 via cantap.

Schneider Electric India

Explore more
Product:
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:
Range: