Video: How do the ATV31/ATV312 logic inputs work when the VFD is in SINK mode?
Issue:
Programming and wiring logic inputs in SINK mode on Altivar 312 or Altivar 31 (ATV312/ATV31) Variable Frequency Drives (VFD).

Product Line:
ATV31 and ATV312

Environment:
All model

Cause:
Developing control scheme

Resolution:
The VFD is in sink mode when the control board DIP switch is in the SINK position.

Internally, the sinking mode connects the logic inputs to the +24V as the common.  A logic input is turned on by connecting it to the COM by means of a dry contact.

Note: When the logic inputs are configured for sink logic, grounding an input signal can result in unintended activation of drive controller functions.

슈나이더 일렉트릭 Korea

Video: How do the ATV31/ATV312 logic inputs work when the VFD is in SINK mode?
Issue:
Programming and wiring logic inputs in SINK mode on Altivar 312 or Altivar 31 (ATV312/ATV31) Variable Frequency Drives (VFD).

Product Line:
ATV31 and ATV312

Environment:
All model

Cause:
Developing control scheme

Resolution:
The VFD is in sink mode when the control board DIP switch is in the SINK position.

Internally, the sinking mode connects the logic inputs to the +24V as the common.  A logic input is turned on by connecting it to the COM by means of a dry contact.

Note: When the logic inputs are configured for sink logic, grounding an input signal can result in unintended activation of drive controller functions.

 

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.