How to completely delete Vijeo Designer Windows PC Runtime?

Issue:
Completely removing Vijeo Designer Windows PC Runtime


Product Line:
Vijeo Designer


Resolution:
Below are the steps to completely delete Vijeo Designer PC Runtime for Window.
You will need to unistall Vijeo Designer Runtime first.

Then delete the following:
delete C:\Program Files\Schneider Electric\Vijeo-Designer\Vijeo-Runtime
delete C:\WINDOWS\57340
delete HKEY_CURRENT_USER\Software\Schneider Electric\Vijeo-Designer Runtime
delete HKEY_LOCAL_MACHINE\SOFTWARE\Schneider Electric\Vijeo-Designer Runtime
delete HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows\CurrentVersion\Run--->RuntimeManager
delete HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows\CurrentVersion\Uninstall\{AC7E8E45-543E-4DA9-BFFD-C140F3E3C83D}
delete HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows\CurrentVersion\Uninstall\{DA0D2543-E9BF-4EF7-A58B-8019CEBFA84B}

If any of the files or registry keys are missing is ok, skip it and go to the next one. Once the deletion are complete, reboot the Magelis iPC or PC.