{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
FAQ 검색
Where can I find the Compatibility Support Matrix for PowerLogic/PowerSCADA Expert/ION products?
Issue
Where can I find the Hardware and Software Support Matrix for PowerLogic, Power Scada Expert, and ION products?

Product Line
Power Monitoring Expert
Power Scada Expert
ION Enterprise
Struxureware Power Monitoring
Summary Report Packs
Event Notification Module
Active Pager Module
SMS
Sequence of Events Recorder

Environment
For New Installations

Cause

Need to know what Hardware and Software Matrix support is needed to install software packages.

Resolution
Power Monitoring Expert 2020 Support
The Windows Operating System versions appy to 32 and 64 bit systems
Operating Systems
Windows 10 Professional/Enterprise
Windows Server 2012 R2 Standard/Enterprise
Windows Server 2016 Standard
Windows Server 2019 Standard
SQL Server EditionsStandAlone ServerDistributed Database Server
SQL Server 2012 ExpressYes
SQL Server 2014 ExpressYes
SQL Server 2016 Express (Included with PME 9.0)Yes
SQL Server 2017 ExpressYes
SQL Server 2012 Standard/Enterprise/Business IntelligenceYesYes
SQL Server 2014 Standard/Enterprise/Business IntelligenceYesYes
SQL Server 2016 Standard/Enterprise/Business IntelligenceYesYes
SQL Server 2017 Standard/Enterprise/Business IntelligenceYesYes

Power Monitoring Expert 9.0 Support
The Windows Operating System versions appy to 32 and 64 bit systems
Operating Systems
Windows 7 Professional/Enterprise (for Engineerng Clients Only)
Windows 10 Professional/Enterprise
Windows Server 2012 R2 Standard/Enterprise
Windows Server 2016 Standard
SQL Server EditionsStandAlone ServerDistributed Database Server
SQL Server 2012 ExpressYes
SQL Server 2014 ExpressYes
SQL Server 2016 Express (Included with PME 9.0)Yes
SQL Server 2017 ExpressYes
SQL Server 2012 Standard/Enterprise/Business IntelligenceYesYes
SQL Server 2014 Standard/Enterprise/Business IntelligenceYesYes
SQL Server 2016 Standard/Enterprise/Business IntelligenceYesYes
SQL Server 2017 Standard/Enterprise/Business IntelligenceYesYes

Power Monitoring Expert 8.2 Support
Operating Systems
Windows 7 Professional/Enterprise, SP1 32/64
Windows 8.1 Professional/Enterprise 64
Windows 10 Professional/Enterprise 64
Windows Server 2008 R2 Standard/Enterprise, SP1 32/64
Windows Server 2012 Standard 64
Windows Server 2012 R2 Standard 64
Windows Server 2016 Standard 64
SQL Server EditionsStandAlone ServerDistributed Database Server
SQL Server 2008 R2 Express, SP3Yes
SQL Server 2012 Express, SP3Yes
SQL Server 2014 Express, SP1, SP2Yes
SQL Server 2016 Express, SP1Yes
SQL Server 2008 R2 Standard/Enterprise, SP3YesYes
SQL Server 2012 Standard/Enterprise/Business Intelligence, SP3YesYes
SQL Server 2014 Standard/Enterprise/Business Intelligence, SP1 SP2YesYes
SQL Server 2016 Standard/Enterprise/Business Intelligence, SP1YesYes
Note that supported 32-bit and 64-bit SQL Server editions can only be installed on supported 32-bit and 64-bit Windows operating systems, respectively. For example, a 32-bit SQL Server edition is not supported on a 64-bit Windows operating system.

Power Monitoring Expert 8.1 Support

Operating Systems
Windows 7 Professional/Enterprise, SP1 32/64
Windows 8.1 Professional/Enterprise 64
Windows 10 Professional/Enterprise 64
Windows Server 2008 R2 Standard/Enterprise, SP1 32/64
Windows Server 2012 Standard, 64
Windows Server 2012 R2 Standard 64
SQL Server EditionsStandAlone ServerDistributed Database Server
SQL Server 2008 R2 Express, SP3Yes
SQL Server 2012 Express, SP2Yes
SQL Server 2014 Express, SP1Yes
SQL Server 2008 R2 Standard/Enterprise, SP3YesYes *1
SQL Server 2012 Standard/Enterprise/Business Intelligence, SP3YesYes *2
SQL Server 2014 Standard/Enterprise/Business Intelligence, SP2YesYes *2
1. Supported for a distributed database server configuration on WindowsServer 2008 R2 Standard/Enterprise SP1.
2. Supported for a distributed database server configuration on WindowsServer 2012 Standard SP1, and on WindowsServer 2012 R2 Standard.
Note that supported 32-bit and 64-bit SQL Server editions can only be installed on supported 32-bit and 64-bit Windows operating systems, respectively. For example, a 32-bit SQL Server edition is not supported on a 64-bit Windows operating system.


Power Monitoring Expert 8.1 DCE Support

Operating Systems
Windows 7 Professional/Enterprise, SP1 32/64
Windows 8.1 Professional/Enterprise 64
Windows 10 Professional/Enterprise 64
Windows Server 2008 R2 Standard/Enterprise, SP1 32/64
Windows Server 2012 Standard, 64
Windows Server 2012 R2 Standard 64
SQL Server Editions
SQL Server 2008 R2 Standard/Enterprise, SP3
SQL Server 2012 Standard/Enterprise/Business Intelligence, SP2
SQL Server 2014 Standard/Enterprise/Business Intelligence, SP1

Note: 32-bit and 64-bit versions are supported. Bites must match between SQL Server and Windows OS (32-bit SQL on 32-bit Windows, 64-bit SQL on 64-bit Windows).

Power Monitoring Expert 8.0 Support
Operating Systems
Windows 7 Professional/Enterprise, SP1 32/64
Windows 8.1 Professional/Enterprise 64
Windows Server 2008 R2 Standard/Enterprise, SP1 32/64
Windows Server 2012 Standard, 64
Windows Server 2012 R2 Standard 64
SQL Server EditionsStandAloneServer Distributed Server
SQL Server 2008 R2 Express, SP3YesNo
SQL Server 2012 Express, SP2YesNo
SQL Server 2014 Express, SP1YesNo
SQL Server 2008 R2 Standard/Enterprise, SP3YesYes *1
SQL Server 2012 Standard/Enterprise/Business Intelligence, SP3YesYes *2
SQL Server 2014 Standard/Enterprise/Business Intelligence, SP2YesYes *2
1. Supported for a distributed database server configuration on WindowsServer 2008 R2 Standard/Enterprise SP1.
2. Supported for a distributed database server configuration on WindowsServer 2012 Standard SP1, and on WindowsServer 2012 R2 Standard.
Note that supported 32-bit and 64-bit SQL Server editions can only be installed on supported 32-bit and 64-bit Windows operating systems, respectively. For example, a 32-bit SQL Server edition is not supported on a 64-bit Windows operating system.

Power Monitoring Expert 7.2.2 Support

Operating Systems and Respective SQL installations
32-bit Windows Operating Systems32-bit Microsoft SQL Server EditionsStandalone ServerDistributed Database Server
Windows 7 Professional/Enterprise, SP1SQL Server 2008 R2 Express, SP2YesNo
SQL Server 2008 R2 Standard/Enterprise, SP2YesNo
SQL Server 2012 Express, SP1YesNo
SQL Server 2012 Standard/Enterprise, SP1YesNo
Windows Server 2008 Standard/Enterprise, SP2SQL Server 2008 R2 Express, SP2YesNo
SQL Server 2008 Standard/Enterprise, SP3YesYes
64-bit Windows Operating Systems64-bit Microsoft SQL Server EditionsStandalone ServerDistributed Database Server
Windows 7 Professional/Enterprise, SP1SQL Server 2008 R2 Express, SP2YesNo
SQL Server 2008 R2 Standard/Enterprise, SP2YesNo
SQL Server 2012 Express, SP1YesNo
SQL Server 2012 Standard/Enterprise, SP1YesNo
Windows Server 2008 Standard/Enterprise SP2, and R2 SP1SQL Server 2008 R2 Express, SP2YesNo
SQL Server 2008 R2 Standard/Enterprise, SP2YesYes
Windows Server 2012 / R2 Standard/EnterpriseSQL Server 2012 Express, SP1YesNo
SQL Server 2012 Standard/Enterprise, SP1YesYes

Struxureware Power Monitoring 7.0.1 Support
Operating Systems and Respective SQL installations
32-bit Windows Operating Systems32-bit Microsoft SQL Server EditionsStandalone ServerDistributed Database Server
Windows 7 Professional Enterprise Editions, SP1SQL Server 2008 R2 Express Editionx
SQL Server 2008 R2 Standard Edition, SP1x
Windows Server 2008 Standard/Enterprise Editions, SP2SQL Server 2008 R2 Express Editionx
SQL Server 2008 Standard/Enterprise Editions, SP2
SQL Server 2008 R2 Standard/Enterprise Editions, SP1
64-bit Windows Operating Systems64-bit Microsoft SQL Server EditionsStandalone ServerDistributed Database Server
Windows 7 Professional Enterprise Editions, SP1SQL Server 2008 R2 Express Editionx
SQL Server 2008 R2 Standard Edition, SP1x
Windows Server 2008 Standard/Enterprise Editions, SP2SQL Server 2008 R2 Express Editionx
SQL Server 2008 Standard/Enterprise Editions, SP2
SQL Server 2008 R2 Standard/Enterprise Editions, SP1
Windows Server 2008 R2 Standard/Enterprise Editions, SP1SQL Server 2008 R2 Express Editionx
SQL Server 2008 Standard/Enterprise Editions, SP2
SQL Server 2008 R2 Standard/Enterprise Editions, SP1

ION Enterprise 6.0 SP1 Support
Operating Systems and Respective SQL installations
32-bit Microsoft Windows Operating Systems32 bit Microsoft SQL Server VersionsStandAloneDistributed DB Server
Windows XP (32-bit) Professional Edition, SP3SQL Server 2005 (32-bit) Express Edition from the ION:E DVDx
Windows Vista (32-1,4) Business/Ultimate/Enterprise Editions, SP2SQL Server 2005 (32 bit) Express Edition from the ION:E DVCx
Windows 7 (32-bit) Professional/Enterprise EditionsSQL Server 2005 (32-bit) Express Edition from the ION:E DVD1x
SQL Server 2005 (32 bit) Standard/Enterprise Editions2x
SQL Server 2008 R2 (32 bit) Standard/Enterprise Editions3x
Windows Server 2003 (32-bit) Standard/Enterprise Editions, SP2SQL Server 2005 (32-bit) Express Edition from the ION:E DVDx
SQL Server 2005 (32-bit) Standard/Enterprise Editions
Windows Server 2003 R2 (32-bit) Standard/Enterprise EditionsSQL Server 2005 (32-bit) Express Edition from the ION:E DVDx
SQL Server 2005 (32-bit) Standard/Enterprise Editions
Windows Server 2008 (32-bit) Standard/Enterprise Editions, SP2SQL Server 2005 (32-bit) Express Edition from the ION:E DVDx
SQL Server 2005(32-big Standard/Enterprise Editions
SQL Server 2008 R2 (32-big Standard/Enterprise Editions711
64 bit Microsoft Windows Operating SystemsMicrosoft SQL Server Versions StandAloneDistributedMinimalist
Windows 7 (64-bit) Professional/Enterprise EditionsSQL Server 2005 (32-bit) Express Edition from the ION:E DVD4xx
SQL Server 2005 (64-bit) Standard/Enterprise Editions5xx
SQL Server 2008 R2 (64-bit) Standard/Enterprise Editions6xx
Windows Server 2008 64 bit Standard/Enterprise Editions, SP2SQL Server 2005 (32-bit) Express Edition from the ION:E DVD8xx
SQL Server 2005 (64-bit) Standard/Enterprise Editions912x
SQL Server 2008 R2 (64-bit) Standard/Enterprise Editions101314
Windows Server 2008 R2 64 bit Standard/Enterprise EditionsSQL Server 2005 (32-bit) Express Edition from the ION:E DVD8xx
SQL Server 2005 (64-bit) Standard/Enterprise Editions912x
SQL Server 2008 R2 (64-bit) Standard/Enterprise Editions1013x

Browser Support for ION E, Struxureware Power Monitoring, and Power Monitoring Expert Support
Browser Support for ION/SPM/PME
Browser Support ION E 6.0SPM 7.0.1PME 7.2.2PME 8.0PME 8.1PME 8.2PME 9.0PME 2020
IE 11
IE 10
IE 9
IE 8
IE 7
IE 6
Chrome 16+
Chrome 20 or later
Chrome 42 and later*
Firefox 14+
Firefox 35 and later*
Microsoft Edge*
Safari 5 and later
Safari 7 and after
Safari 8 and after

* The browsers support the web application framework, and Dashboards, Diagrams, and Trends
applications. Alarms and Tables are dependent on browser support of the Silverlight plugin.

Power Scada Expert Support
Operating SystemsPLS 7.10PLS 7.20PSE 7.30PSE 7.40PSE 8.0PSE 8.1PSE 8.2PSE 9.0
Windows XP, SP3 ProfessionalYesYesYesNoNoNoNoNo
Windows Server 2003, SP2 Standard/EnterpriseYesYesYesNoNoNoNoNo
Windows Server 2003 R2, SP1YesYesNoNoNoNoNoNo
Windows Vista, SP2YesYesYesNoNoNoNoNo
Windows 7, SP1 Professional/EnterpriseNoYesYesYesYesYes *4Yes *4Yes *5
Windows Server 2008, SP2 Standard/EnterpriseNoYesYesYesNoNoNoNo
Windows Server 2008 R2, SP1NoYesYesYesYesYesYesNo
Windows 8NoNoYes *1/2YesYesYes *4Yes *3/4No
Windows 8.1NoNoNoNoYes *2Yes *4Yes *4No
Windows Server 2012NoNoYes *1/2YesYesYesYesYes
Windows Server 2012 R2NoNoNoNoYes *2YesYesYes
Windows 10NoNoNoNoNoNoYes *4Yes *5
Windows Server 2016NoNoNoNoNoNoYesYes
1. Service Pack 1 for the operating system is required
2. Available with PowerSCADA Expert Service Release 1
3. Not supported by Advanced Reporting and Dashboards (PME)
4. Not supported by PowerSCADA Anywhere
5. Support for 64-bit Windows only


Summary Report Pack Support
Platform Compatibility
✓=SupportedSRP 2.1SRP 3.0 SRP 3.0.1SRP 3.2SRP 4.0 SRP 4.2SRP 4.3SRP 5.1SRP 5.2SRP 6.0
ION Enterprise 6.0 SP1xxxxxxxxx
SPM 7.0xxxxxxx
SPM 7.0.1xxxxxxxx
PME 7.2xxxxxxxx
PME 7.2.1xxxxxxxx
PME 7.2.2xxxxxxxx
PME  8.0xxxxxxxx
PME 8.2xxxxxxxxx
PME 9.0xxxxxxxxx
SQL Server
Microsoft SQL Server 2005 (32-bit)xxxxxx
Microsoft SQL Server 2008 (32-bit & 64-bit)xx
Microsoft SQL Server 2008 R2 (64-bit)
Microsoft SQL Server 2008 R2 Expressxxxx
Microsoft SQL Server 2012 AIxxxx

Sequence of Events Recorder (SER) Support
DevicesSER 8.0SER 7.5/7.5.1SER 7.3
CM4000 (SER and Standard Alarms)
Multilin (489, 745, 750,760)
Sepam (20 40 80)
Sepam (1000 2000)xx
Moghnahan Protime
Moghnahan PLC
Cyber Sciences 3200
Cyber Sciences 2408
Power Meter 870
Schweitzer Devices (300G,351A,700G,710,75 A)xx
HistorianSER 8.0SER 7.5/7.5.1SER 7.3
Event Logging
"Live" Current Events view
"Historical" Events View
Event Sorting and Filtering for analysis
System Healthxxx
"Live Current Events view
Historical" Events View
Event Sorting and Filtering for analysis
Operating SystemSER 8.0SER 7.5/7.5.1SER 7.3
Windows Server 2012/2012 R2xx
Windows 8/8.1xx
Windows Server 2008 R2 (64bit)
Windows Server 2008 (64bit)
Windows Server 2008 (32bit)
Windows 7 (64bit)
Windows 7 (32bit)
Windows Server 2003xx
Windows Vista (32bit)xx
Windows XPxx
SQL ServerSER 8.0SER 7.5/7.5.1SER 7.3
Microsoft SQL Server 2012xx
Microsoft SQL Server 2008 R2 (64bit)x
Microsoft SQL Server 2008 R2 (32bit)x
Microsoft SQL Server 2008x
Microsoft SQL Server 2005 (32bit)xx
Browser SupportSER 8.0SER 7.5/7.5.1SER 7.3
lE 11xx
IE 10xx
IE 9xx
IE 8xxx
IE 8 (Compatibility Mode)x
Chrome 16+xx
Firefox 14+xx
LanguagesSER 8.0SER 7.5/7.5.1SER 7.3
English
*SER 7.5.1 contains the same feature set at SER 7.5, but includes a hotfix related to installs on distributed systems.

Event Notification Module Support
PlatformENM 8.3ENM 8.2ENM 8.0ENM 7.1ENM 7.0ENS 6.4
PME 9.0xxxxx
PME 8.0xxxxx
PSE 8.0xxxxx
PSE v7.40 SR1xxxx
PSE v7.40xxxx
PLSCADA v7.20xx
PLS v7.20 SR1xxx
PSE 7.30/SR1xxx
PLSCADA v7.10xxxxxx
CitectSCADA v7.20xxxxxx
CitectSCADA v7.10xxxxxx
Vijeo Citect v7.20x
Vijeo Citect v7.10xxxxxx
SPM 7.0/7.0.1xx
PME 7.20xxx
ION Enterprise 6.0/6.0 SP1xxxx
SMS 4.3xxxxx
Operating SystemENM 8.3ENM 8.2ENM 8.0ENM 7.1ENM 7.0ENS 6.4
Windows Server 2012 R2 (64bit)xxxx
Windows Server 2012 (64bit)xxxx
Windows Server 2008 R2 (64bit)x
Windows Server 2008 (64bit)x
Windows Server 2008 (32bit)
Windows 8.1 (64bit)xxxx
Windows 8 (64(bit)xxxx
Windows 7 (64bit)x
Windows 7 (32bit)
Windows Server 2003xxxxx
Windows Vista (32bit)xxxxx
Windows XPxxxxx
Operating Systems Support for Event Notification Module
SQL ServerENM 8.3ENM 8.2ENM 8.0ENM 7.1ENM 7.0ENS 6.4
SQL Server 2014 Standard/Enterprisexxxxx
SQL Server 2014 Expressxxxxx
SQL Server 2012 Standard/Enterprisexx
SQL Server 2012 Expressxxxxx
SQL Server 2008 R2 (64bit)x
SQL Server 2008 R2 (32bit)
SQL Server 2008 xxxx
SQL Server 2008 SP2xxxxx
SQL Server 2005 (32bit)xxxxx
Browser Support for Event Notification Module
Browser SupportENM 8.3ENM 8.2ENM 8.0ENM 7.1ENM 7.0ENS 6.4
IE 11xxx
IE 10xxx
IE 9xxx
IE 8xxxxxx
IE 8 (Compatibility Mode)xxx
Chrome 20+xxxx
Chrome 16+xxxx
Firefox 14+xxx

System Manager Software (SMS) 4.3 Support
32-bit Microsoft Windows Operating Systems32-bit Microsoft SQL Server VersionsSupported?
Windows XP (32-bit) Professional Edition, SP3SQL Server 2005 (32-bit) Standard/EnterpriseYes
Windows Vista (32-bit)NoneNo
Windows 7 (32-bit) - Professional/Enterprise NoneNo
Windows Server 2003 (32-bit) - Standard/Enterprise Editions, SP2SQL Server 2005 (32-bit) Standard/EnterpriseYes
Windows Server 2003 R2 (32-bit) - Standard/Enterprise EditionsSQL Server 2005 (32-bit) Standard/EnterpriseYes
Windows Server 2008 (32-bit) - Standard/Enterprise Editions, SP2SQL Server 2005 (32-bit) Standard/EnterpriseYes
64-bit Microsoft Windows Operating SystemsMicrosoft SQL Server VersionsSupported?
Windows Vista (64-bit)NoneNo
Windows 7 (64-bit) - Professional/Enterprise EditionsNoneNo
Windows Server 2008 (64-bit) - Standard/Enterprise Editions, SP2NoneNo
Windows Server 2008 R2 (64-bit) - Standard/Enterprise EditionsNoneNo
1. Supported for a distributed database server configuration on WindowsServer 2008 R2 Standard/Enterprise SP1.
2. Supported for a distributed database server configuration on WindowsServer 2012 Standard SP1, and on WindowsServer 2012 R2 Standard.
Note that supported 32-bit and 64-bit SQL Server editions can only be installed on supported 32-bit and 64-bit Windows operating systems, respectively. For example, a 32-bit SQL Server edition is not supported on a 64-bit Windows operating system.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
유용한 문서
자세히 알아보기
제품군