What does the 'Modbus Exception Code 03 Illegal Data Value' error mean when writing to a External Modbus Control Register on a 7650?

Product Line
ION7650/7550

Environment
Register Writing

Resolution
The meter is locked into a Read-Only mode when the password security is anything other than the default of 0 (zero).  To write to an External Modbus control registers requires password security to either be disabled, or set to 0.

슈나이더 일렉트릭 Korea

What does the 'Modbus Exception Code 03 Illegal Data Value' error mean when writing to a External Modbus Control Register on a 7650?

Product Line
ION7650/7550

Environment
Register Writing

Resolution
The meter is locked into a Read-Only mode when the password security is anything other than the default of 0 (zero).  To write to an External Modbus control registers requires password security to either be disabled, or set to 0.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.