What needs to be done to use Blokset at high altitudes (2000m, 3000m, etc.)?
It is possible to use BlokSeT at higher altitude >2000m. We have to apply the derating value as informed in the latest BlokSeT catalog.
As per the table below, derating to be applied for circuit breaker and rated voltage.