Data Center Expert | Why does StruxureWare not accept my One Time passcode?

Issue
StruxureWare Data Center Expert is not accepting my One Time passcode.

Product Line
StruxureWare Data Center Expert (DCE)

- Basic Appliance (AP9465)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)

StruxureWare Central (SWC)
InfraStruXure Central (ISXC)

Environment
StruxureWare Data Center Expert (all versions)
StruxureWare Central (all versions)
InfraStruXure Central (all versions)

Cause
SturuxureWare / EcoStruxure Data Center Expert requires a 64 character license key that is created at EcoStruxure IT Entitlements portal at https://ecostruxure-it-entitlements.se.com/ by combining the passcode and the Data Center Expert's MAC address.


Resolution:

The Passcode you receive when purchasing a license key is not the actual license.
Below you will find instructions to convert the passcode to a license key.


1. In a web browser, navigate to EcoStruxure IT Entitlements portal at https://ecostruxure-it-entitlements.se.com/
2. Log in to the site using e-mail and password or register.
3. Follow the instructions located on the Welcome page.

슈나이더 일렉트릭 Korea

Data Center Expert | Why does StruxureWare not accept my One Time passcode?

Issue
StruxureWare Data Center Expert is not accepting my One Time passcode.

Product Line
StruxureWare Data Center Expert (DCE)

- Basic Appliance (AP9465)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)

StruxureWare Central (SWC)
InfraStruXure Central (ISXC)

Environment
StruxureWare Data Center Expert (all versions)
StruxureWare Central (all versions)
InfraStruXure Central (all versions)

Cause
SturuxureWare / EcoStruxure Data Center Expert requires a 64 character license key that is created at EcoStruxure IT Entitlements portal at https://ecostruxure-it-entitlements.se.com/ by combining the passcode and the Data Center Expert's MAC address.


Resolution:

The Passcode you receive when purchasing a license key is not the actual license.
Below you will find instructions to convert the passcode to a license key.


1. In a web browser, navigate to EcoStruxure IT Entitlements portal at https://ecostruxure-it-entitlements.se.com/
2. Log in to the site using e-mail and password or register. 
3. Follow the instructions located on the Welcome page.
 

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.