How to set up a fault reset function on ATV630 Process drive?
Issue:
Fault reset function on the ATV630
Product Line:
Altivar ATV630
Environment:
All Process drives
Cause:
Fault reset function needed
Resolution:
Go into Menu 5 complete settings and enter
Go down to submenu 5.11 Error/Warning Handing and enter
Go to Fault Reset and Enter.
Go to Fault Reset Assignment
Choose digitial input desired to act as a fault reset.