{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.

FAQ 검색

Video: What would cause the ATS48 to show RDY even with a run command?

Issue:
Troubleshooting a RDY (ready) status following a run command on the Altistart ATS48 Soft Starter by verifying supply voltages and wiring with a multi meter.

Product Line:
Altistart ATS48

Environment:
All models

Cause:
The Soft starter is stuck on RDY and will not run with a run command.

Resolution:
Confirmed that the +24V supply is still there.  Measure between 24V and COM on soft start.  If necessary remove wires off the terminals.
If in 2 wire control mode, make sure you have 24vdc on Run and Stop.
If you are doing 3 wire control make sure you have +24vdc on Stop and you are pulsing Start to get the soft starter to start.  Stop is normally closed and start is normally open push button contacts.
If you are doing NET control over a network  you will need to make sure +24vdc is supplied to the Stop input at all times.

슈나이더 일렉트릭 Korea

첨부 파일

instruction bulletin enclosed ATS48.pdfinstruction bulletin enclosed ATS48.pdf [1.3 MB]
자세히 알아보기
제품군
자세히 알아보기
제품군