FAQ 검색
High CPU spike on FrameworkServices
Issue
User is observing very high CPU usage from the FrameworkService
Product Line
Power Monitoring Expert 8.0
Environment
Windows Task Manager
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
1) Download the zip file attached to this article
2) Backup the files listed at the bottom of this email
3) Stop all of the Power Monitoring Expert Services (They start with ION and ApplicationModules)
4) Replace the dll's with the attached ones in the corresponding locations of the Power Monitoring Expert Installation (Application Server).
5) Restart the services.
The list of files contained in this hotfix include:
...\Power Monitoring Expert\Applications\AlarmConfiguration\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\ApplicationFramework\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\EWS\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\HierarchyManager\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\RateEditor\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\SystemDataService\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\TrendsWebServices\bin\Framework.Common.dll
...\Power monitoring Expert\system\bin\Framework.Common.dll
...\Power monitoring Expert\system\ReportDataService\bin\Framework.Common.dll
...\Power monitoring Expert\Web\bin\Framework.Common.dll
User is observing very high CPU usage from the FrameworkService
Product Line
Power Monitoring Expert 8.0
Environment
Windows Task Manager
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
1) Download the zip file attached to this article
2) Backup the files listed at the bottom of this email
3) Stop all of the Power Monitoring Expert Services (They start with ION and ApplicationModules)
4) Replace the dll's with the attached ones in the corresponding locations of the Power Monitoring Expert Installation (Application Server).
5) Restart the services.
The list of files contained in this hotfix include:
...\Power Monitoring Expert\Applications\AlarmConfiguration\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\ApplicationFramework\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\EWS\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\HierarchyManager\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\RateEditor\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\SystemDataService\bin\Framework.Common.dll
...\Power monitoring Expert\Applications\TrendsWebServices\bin\Framework.Common.dll
...\Power monitoring Expert\system\bin\Framework.Common.dll
...\Power monitoring Expert\system\ReportDataService\bin\Framework.Common.dll
...\Power monitoring Expert\Web\bin\Framework.Common.dll
게시 대상:슈나이더 일렉트릭 Korea
첨부 파일
자세히 알아보기
제품군
자세히 알아보기
제품군