Why does Vijeo Designer report Error 2897 when I build the application?

Issue:
Somachine / Vijeo Designer reports Error 2897 when I build the application when I only have one device connected to COM1.

Product Line:
Vijeo Designer (all versions), SoMachine (all versions)

Resolution:
This build error occurs in Vijeo Designer when SoMachine has the "SoMachine_Network_Manager" added under COM1 of Somachine configuration.
Why does Vijeo Designer report Error 2897 when I build the application?
To resolve this issue, delete the SoMachine_Network_Manager under COM1 in Somachine and the Vijeo Designer application will build properly.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

Why does Vijeo Designer report Error 2897 when I build the application?

Issue:
Somachine / Vijeo Designer reports Error 2897 when I build the application when I only have one device connected to COM1.

Product Line:
Vijeo Designer (all versions), SoMachine (all versions)

Resolution:
This build error occurs in Vijeo Designer when SoMachine has the "SoMachine_Network_Manager" added under COM1 of Somachine configuration.
Why does Vijeo Designer report Error 2897 when I build the application?
To resolve this issue, delete the SoMachine_Network_Manager under COM1 in Somachine and the Vijeo Designer application will build properly.

 

If this FAQ did not solve your issue, you can chat with us at  chat with us  or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.