{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
FAQ 검색
Video: Why are my configuration settings missing after a power cycle on a HMIG5U/HMIG5U2?
Issue:
Configuration settings missing after a power cycle on a HMIG5U/HMIG5U2

Product Line:
HMIG5U, HMIG5U2, Smart iPC, iPC with CFAST or Flash Card as disk drive.

Resolution:
When the EWF (Enhanced Write Filter) is activated for the system drive (C:\ ) on a HMIG5U/HMIG5U2 or any iPC with a Compact Flash card or CFast card as the system drive, any sort of file change or configuration setting made to C:\ will be lost after a power cycle. The only way to retain these changes after a power cycle is to commit them to the disk drive using the EWF configuration tool. Alternatively, you can deactivate the EWF before making any changes.



To deactivate the EWF, please follow this procedure below:

1) In the task tray, look for the icon of a drive and a lock.
2) Click on this icon to open the EWF Configuration Tool.
3) Select the drive letter and press the "Configure" button.
4) Select the drive letter again and notice "Pending command" is activated.
5) Select in the drop down menu "Commit and disable live"
6) Press the "Apply" button and then press the "OK" button.
7) Notice that the EWF is now deactivate.

Once the EWF is deactivated, you can make all your changes to C:\ and they will be retained after a power cycle. Once you are done making changes to the C:\, remember to re-activate the EWF to continue with the system drive protection.

To re-activate the EWF, it is the same process as shown above with the exception that you will now choose to activate the EWF.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
유용한 문서
자세히 알아보기
제품군