What are the maximum DNP base points for ION8650 A, B and C Meters?
Issue
ION8650 meters do not allow the configuration of more than 100 DNP base points from ION Setup
It will actually let you keep adding to the parameter map but when you exit setup assistant it throws this message:
"The following modules are off-line and may indicate an improperly configured feature in the device" as shown below:

What are the maximum DNP base points for ION8650 A, B and C Meters

When you try to bring the modules online, the following error message is displayed:
"Too many DNP points configured in DSE" as shown below:

What are the maximum DNP base points for ION8650 A, B and C Meters

What are the maximum DNP base points for ION8650 A, B and C Meters

Product Line
ION 8650 Meters A, B and C
ION Setup

Environment
ION8650 DNP Static Points

Cause
Unable to configure over a 100 DNP base points on an ION8650s in ION Setup

Resolution
The limitation for DNP base points on ION 8650 meters is 100 as stated below:
What are the maximum DNP base points for ION8650 A, B and C Meters
This information can be found under the Powerlogic ION8650 DNP 3.0 Device Profile document, which can be downloaded from the link below

http://download.schneider-electric.com/files?p_Reference=70022-0126-00&p_EnDocType=User guide&p_File_Id=27606449&p_File_Name=70022-0126-00.pdf

슈나이더 일렉트릭 Korea

What are the maximum DNP base points for ION8650 A, B and C Meters?
Issue
ION8650 meters do not allow the configuration of more than 100 DNP base points from ION Setup
 It will actually let you keep adding to the parameter map but when you exit setup assistant it throws this message:
"The following modules are off-line and may indicate an improperly configured feature in the device" as shown below:

                  What are the maximum DNP base points for ION8650 A, B and C Meters

When you try to bring the modules online, the following error message is displayed:
"Too many DNP points configured in DSE" as shown below:

                 What are the maximum DNP base points for ION8650 A, B and C Meters
       
                What are the maximum DNP base points for ION8650 A, B and C Meters

Product Line
ION 8650 Meters A, B and C
ION Setup

Environment
ION8650 DNP Static Points

Cause
Unable to configure over a 100 DNP base points on an ION8650s in ION Setup

Resolution
The limitation for DNP base points on ION 8650 meters is 100 as stated below:
What are the maximum DNP base points for ION8650 A, B and C Meters
This information can be found under the Powerlogic ION8650 DNP 3.0 Device Profile document, which can be downloaded from the link below

 http://download.schneider-electric.com/files?p_Reference=70022-0126-00&p_EnDocType=User guide&p_File_Id=27606449&p_File_Name=70022-0126-00.pdf

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.