What are the maximum number of fault current operations Ringmaster and GenieEvo will clear?
The number of faults that a circuit breaker can clear will depend on the level of fault current being interrupted.

Ringmaster: -
  • 16kA - the circuit breaker is designed to clear a maximum number of 11 times at 16kA fault current
  • 21kA - the circuit breaker is designed to clear a maximum number 10 times at 21kA fault current

GenieEvo is designed to clear a maximum of 100 faults at 25kA.

The fault current rating of the unit is detailed on the unit rating plate.

슈나이더 일렉트릭 Korea

What are the maximum number of fault current operations Ringmaster and GenieEvo will clear?
The number of faults that a circuit breaker can clear will depend on the level of fault current being interrupted.

Ringmaster: -
  • 16kA - the circuit breaker is designed to clear a maximum number of 11 times at 16kA fault current
  • 21kA - the circuit breaker is designed to clear a maximum number 10 times at 21kA fault current
     

GenieEvo is designed to clear a maximum of 100 faults at 25kA.

The fault current rating of the unit is detailed on the unit rating plate.

 

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.