Issue:
Set up Plus/Minus Speeds on the Altivar Process Drive.
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Resolution:
To Program the +/- Speeds
Set up Plus/Minus Speeds on the Altivar Process Drive.
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Resolution:
To Program the +/- Speeds
- [Complete settings] [Command and Reference]
- Set [Freq Switch Assign] rFC to [Ref Freq Channel 2] FR2
- Set [Ref Freq Channel 2] FR2 to [Ref Frequency via DI] UPdt
- Go to [Complete settings] [Generic functions] [+/- speed]
- Assign [+ Speed Assign] USP
- Assign [- Speed Assign] dSP
- Assign [Ref Frequency Save] Str
To adjust the increment of plus and minus speed, adjust the ACC and DEC. If ACC is set to 6 seconds, it will ramp 10 Hz for every second that the +speed is active (60Hz range / 6sec = 10Hz/sec). Keep it active for 6 seconds and output will reach 60 Hz. To make +speed increase at a slower rate, increase ACC. To make it faster, decrease ACC. The same logic applies to -speed and DEC.
게시 대상:슈나이더 일렉트릭 Korea



