What are the recommended overload current temporary or permanent, RM22JA21MR?
Here is the overload current capacity info.

Short time overload for 3s
Max Permissible Overload Current
ReferenceE1-ME2-ME3-M
RM35JA31MW400mA for <3s1000mA for <3s2200mA for <3s
RM35JA32MW4A for <3s12A for <3s20A for <3s
RM22JA21MR900mA for <3s1400mA for <3s2000mA for <3s
RM22JA31MR900mA for <3s1400mA for <3s2000mA for <3s
RM35JA32MR4A for <3s12A for <3s20A for <3s
RM35JA32MT4A for <3s12A for <3s20A for <3s



Continuous overload
Max Permissible Continuous Overload Current
ReferenceE1-ME2-ME3-M
RM35JA31MW360mA900mA2000mA
RM35JA32MW2A7.5A17A
RM22JA21MR800mA1200mA1600mA
RM22JA31MR800mA1200mA1600mA
RM35JA32MR2A7.5A17A
RM35JA32MT2A7.5A17A