How can I get 5% line impedance for the ATV630 Process Drives?

Article available in these languages: 스페인어

Issue:
Customer is looking for equivalent to 5% line reactor on the Altivar Process drive.

Product line:
ATV630, ATV600, Altivar Process

Resolution:
The drive's standard internal DC choke plus a 3% line reactor.  Adding an external line reactor will yield a 5% line impedance equivalence.
Schneider Electric does not offer Line reactors for the Altivar Process Drives.  Please contact a manufacturer, such as MTE Corp, for selection.