{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
FAQ 검색
Why will the ATV61/71 Logic Input not reset the External Fault?
Issue:
The ATV71 has External Fault assigned to LI5.  When active, LI5 trips the drive into External Fault, EPF1.  When activating Fault Reset on assigned LI4, the fault is not reset.

Product line:
Altivar 61 Altivar 71

Environment:
All

Cause:
The fault reset needs to come from the assigned Command Channel.

Resolution:
In this case, Command Channel 1 was assigned to a Communications network. So, a Fault Reset needs to come from the Communications Network.
Fault reset by Logic Input is not possible unless the active command channel is Terminals.

Consider temporarily switching the Command Channel to Terminals and then close Logic Input assigned to Reset, or switch to HMI mode and use the local Stop/Reset button (push twice) to reset.

See description / options on the attached file.

슈나이더 일렉트릭 Korea

첨부 파일
ATV61 reset function not working by Logic input.pdf [48.93 KB]
자세히 알아보기
제품군
유용한 문서
자세히 알아보기
제품군