On the ATV630 and ATV930 process drives, why can't the digital input assignments be changed?
Issue:
ATV630/ATV930 the digital input assignments are not changing in the Input/Output menu?

Product Line:
Altivar Process, Altivar 630, ATV630, Altivar 930, ATV930

Environment:
All models

Cause:
Attempting to change DIx assignments in the COMPLETE SETTINGS > INPUT/OUTPUT menu

Resolution:
The digital input assignments in the INPUT/OUTPUT menu are read only.  To change an assignment, you need to go to the desired function and then assign an Input to the function. Example: to assign Reverse to DI2, you need to go to "Reverse assign" in the Command and Reference menu, and change that to DI2.

Link to the ATV600 programming manual:  https://download.schneider-electric.com/files?p_Doc_Ref=EAV64318
Link to the ATV900 programming manual;  https://www.se.com/us/en/download/document/NHA80757/

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.