{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.

FAQ 검색

Galaxy 5000, Galaxy 5500; Dust Covers



Issue:
It has been determined that dust and other foreign conductive particles have been getting inside the UPS during shipping or from site construction projects during installation.

Product line:
Galaxy 5000, Galaxy 5500

Environment:
All models, all serial numbers

Cause:
Conductive dust and particles negatively affect system operation by increasing component temperatures and reducing dielectric strength.



Resolution:
Temporary front and top covers are being applied to Galaxy 5000 units prior to shipping to protect the unit from foreign particles.



FRONT dust protection cover



TOP dust protection cover
Only Schneider Electric Certified Field Service Engineers are authorized to remove this cover.

Bottom Portion can be lifted to provide access to input / output wiring section.




슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군