브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to detect the Vijeo Designer application located on the secondary drive at the HMIG5U startup?
Sometimes, on Magelis HMIG5U, when using the secondary drive (SD card) to store the Vijeo Designer application, the application doesn’t start.
This behavior appears when the EWF is enabled (Enhanced Write Filter). Due to this setting, the HMIG5U doesn’t detect the SD card quick enough and Vijeo Designer Runtime starts without loading the user application located on the SD card. In order to avoid this inconvenient, we can delay the startup of VJD Runtime.

To do that, you have to:
  • Disable the EWF
  • Create a folder "C:\DelayStart"
  • Copy/Paste the attached files: "DelayStart.exe" and "DelayStart.ini"
  • Open the file "DelayStart.ini" and check that "InstallAutorun=1"
  • Run "DelayStart.exe"
  • Disable the AutoStart of VJD Runtime via the VJD Runtime Manager
  • Enable the EWF and restart the Magelis HMIG5U.

After restarting the Magelis HMIG5U, you should have a new command in the Startup menu as described in the attached screenshot.

슈나이더 일렉트릭 Korea

첨부 파일
DelayStart.png [200.87 KB]
Startup_menu.png [655.92 KB]
DelayStart.zip [403.41 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.