The BMXNOE0100 Global Data service and GMRP
Issue
BMXNOE0100 Global Data service and GMRP
Product Line
BMXNOE0100 BMXNGD0100
Environment
Control Expert, Unity Pro 12
Resolution
The BMXNOE0100 Global Data Service only supports GMRP. The GMRP multicast registration will not work with switches that only support IGMP.
BMXNOE0100 Global Data service and GMRP
Product Line
BMXNOE0100 BMXNGD0100
Environment
Control Expert, Unity Pro 12
Resolution
The BMXNOE0100 Global Data Service only supports GMRP. The GMRP multicast registration will not work with switches that only support IGMP.