Issue
Customer would like to configure separate overcurrent protection for transformer primary and secondary on Sepam T87
Product Line
Sepam T87
Environment
SFT2841
Resolution
Customer would like to configure separate overcurrent protection for transformer primary and secondary on Sepam T87
Product Line
Sepam T87
Environment
SFT2841
Resolution
- (Sepam settings -> CT/VT sensors) Configure the CT/VT Sensors. Note the locations of sensors (Ia, Ib, Ic) and sensors (I’a, I’b, I’c)
- (Protection settings -> 50/51) Select desired primary (Ia, Ib, Ic) or secondary (I’a, I’b, I’c) sensors for each unit from the “Measurement Origin” dropdown menu. These correspond to the line diagram configured in step 2
- (Protection settings -> 50/51) Verify desired measurement origin is selected, click the corresponding “On” checkbox and click “Apply” to apply changes
- (Protection settings -> 50/51) Configure tripping curves for each unit as required
게시 대상:슈나이더 일렉트릭 Korea

