{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.

FAQ 검색

What causes a Ground short circuit fault on an ATS48 and how quickly does the fault relay change states afterwards?

Issue:
How does the Altistart 48 detect a Ground Short Circuit?

Product line:
ATS48 series soft starter.

Enironment:
All models, All serial numbers.

Cause:
Information in current literature does not provide specific information on how the fault is triggered.

Resolution:
The Starter measures the current on each phase of the output.  Current out should be equal to current. When measuring the current draw on all 3 phases simultaneously, the total current should be 0 amps.   If the measured difference in current between all three phases is greater than 25% of the setting of the IN parameter for more than 100ms, the fault is triggered. Once the fault is triggered it takes around 16ms for the relay to close.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
Altistart 48Enclosed ATS48
자세히 알아보기
제품군
Altistart 48Enclosed ATS48