Issue:
Need to confirm that the Altivar Process drive is recognizing the digital inputs.
Product line:
ATV600, ATV900, Altivar Process
Environment:
n/a
Cause:
Troubleshooting drive
Resolution:
Push the Home button to get to the Main Menu.
From the Main Menu, navigate to Display -> I/O Map -> Digital Input Map.
It will now display the status of the STOA, STOB and Digital Inputs 1 thru 8. The contact is closed if the Input shows High (or up). The contact is open if the input shows Low (or down).
Note: From this menu, highlight and enter each input to check which functions are assigned to it.