Can all contact blocks be used for the 30mm range joysticks? [Video]

Question:
Can all contact blocks be used for the 30mm range joysticks?

Product String Reference:

  1. Top Level > Product Category > Industry > Industry Control & Drives > Control, Relays & Sign > Diameter 30.
  2. Top Level > PR_Product_OPS_Structure > Pushbuttons, Switches, Pilot Lights and Joysticks > 30mm Push Buttons > Harmony 30mm 9001K Metal Push Buttons

Objective:
The objective of this video is to provide an in-depth analysis of contact blocks and their application.



Product Line:
IDSIG - CONTROL, RELAYS & SIGN.

Environment:
N/A

Resolution:

When used in conjunction with a Harmony range push button, the:
  1. Combination N/O + N/C, N/C opens and N/O closes
  2. N/C contact opens when push button is depressed
  3. N/O contact closes when push button is depressed

When used in conjunction with the 30mm range joystick application.
  1. Combination N/O + N/C will stay open so that it is neither open nor closed
  2. N/C contact is open
  3. N/O contact is open
When the joystick is maneuvered, the:
  1. Combination N/O + N/C will close at different positions of the joystick handle.
  2. N/C will close
  3. N/O will close

As such, these contacts do not act in the same way for a joystick as they do for the Harmony range push button application.

슈나이더 일렉트릭 Korea

Can all contact blocks be used for the 30mm range joysticks? [Video]

Question:
Can all contact blocks be used for the 30mm range joysticks?
 
Product String Reference:

  1. Top Level > Product Category > Industry > Industry Control & Drives > Control, Relays & Sign > Diameter 30.
  2. Top Level > PR_Product_OPS_Structure > Pushbuttons, Switches, Pilot Lights and Joysticks > 30mm Push Buttons > Harmony 30mm 9001K Metal Push Buttons
 
Objective:
The objective of this video is to provide an in-depth analysis of contact blocks and their application.


 
Product Line:
IDSIG - CONTROL, RELAYS & SIGN.
 
Environment:
N/A
 
Resolution:
 
When used in conjunction with a Harmony range push button, the:
  1. Combination N/O + N/C, N/C opens and N/O closes
  2. N/C contact opens when push button is depressed
  3. N/O contact closes when push button is depressed
 
When used in conjunction with the 30mm range joystick application.
  1. Combination N/O + N/C will stay open so that it is neither open nor closed
  2. N/C contact is open
  3. N/O contact is open
When the joystick is maneuvered, the:
  1. Combination N/O + N/C will close at different positions of the joystick handle.
  2. N/C will close
  3. N/O will close

As such, these contacts do not act in the same way for a joystick as they do for the Harmony range push button application.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.