Issue
Procedure to adding a remote drop to an M580 configuration in Unity Pro.
Product Line
Modicon M580 ePAC (Ethernet Programmable Automation Controller)
Environment
Unity Pro
Resolution
To add a remote drop to an M580 configuration, you need to open the EIO bus. Once the EIO bus is open you can double-click the small box. That will launch a window where you can select the appropriate rack and CRA.
Note: There is a similar small box directly under the local rack in PLC bus window. Double-clicking this box does NOT add a remote drop but rather an extended rack.
Procedure to adding a remote drop to an M580 configuration in Unity Pro.
Product Line
Modicon M580 ePAC (Ethernet Programmable Automation Controller)
Environment
Unity Pro
Resolution
To add a remote drop to an M580 configuration, you need to open the EIO bus. Once the EIO bus is open you can double-click the small box. That will launch a window where you can select the appropriate rack and CRA.
Note: There is a similar small box directly under the local rack in PLC bus window. Double-clicking this box does NOT add a remote drop but rather an extended rack.
게시 대상:슈나이더 일렉트릭 Korea



