{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.

FAQ 검색

Easy-UPS reports bDC <Battery Disconnected>

Issue: Easy-UPS reports bDC <Battery Disconnected> during online operation with battery properly connected

Product lines: SRV1KI, SRT2KI, SRV3KI, SRV1KRI, SRV2KRI, SRV3KRI, SRC1KI, SRC1I-AR, SRC2KI, SRC2KI-AR, SRC1KUXI-IN, SRC1KUXI, SRC1KUKXIX84

Cause: The UPS performs an internal battery self-check every 5 minutes. If the UPS detects the battery voltage has deviated outside the acceptable threshold, the UPS will report bDC <Battery Disconnected>. The alert will auto resolve within 5 minutes at the next battery self-check.

Resolution: Use the attached firmware upgrade guide and the appropriate firmware file to update the UPS firmware and resolve the bDC event.

슈나이더 일렉트릭 Korea

첨부 파일

Update firmware and software Easy-UPS 1-3kVA.7zUpdate firmware and software Easy-UPS 1-3kVA.7z [179.19 KB]
Easy-UPS SRV firmware upgrade.pdfEasy-UPS SRV firmware upgrade.pdf [296.17 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군