When setting up Encoder communication in Unity Pro, he faced the following problems.
If you add one connection as shown in the attached picture, 'Add Connection' is disabled.
- Product Line
- Environment
- Resolution
There is a workaround which will allow to configure multiple connections: Add the following keyword under the [Device] section of EDS file, it will enable the multiple connections addition.
243_AdvanceGeneric = 1;
And then remove the previous EDS file in Unity Pro, add the new one. Now it’s available to add more connection.