What are the maximum Session/Subscription for the BMENUA0100 with the firmware version 1.01.50?
1.    Issue
Client wants to know what are the maximum Session/Subscription for the BMENUA0100 ?

2.    Product Line
Firmware version 1.01.50

3.    Environment
BMENUA0100

4.    Resolution

Here you are the limitation Session/Subscription for the BMENUA0100

The maximum session to be open is 3.
The maximum subscription to be open per session is 4.

Total subscription is 12.

슈나이더 일렉트릭 Korea

What are the maximum Session/Subscription for the BMENUA0100 with the firmware version 1.01.50?
1.    Issue
Client wants to know what are the maximum Session/Subscription for the BMENUA0100 ?

2.    Product Line
Firmware version 1.01.50

3.    Environment
BMENUA0100

4.    Resolution

Here you are the limitation Session/Subscription for the BMENUA0100

The maximum session to be open is 3.
The maximum subscription to be open per session is 4.

Total subscription is 12.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.