{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
FAQ 검색
What are the rules to be followed for SPD mounting inside BlokSeT equipment?
Below are the rules which we need to follow for the SPD mounting inside BlokSeT.
  1. The surge arrester connections between the network (through the disconnection device) and the earth terminal block does not exceed 50 cm.
  2. 50cm rules of cable length is derived based on the inductance of the cable. So, the inductance of wire plays a major role to decide the cross section and length of cable.
  3. The length of cable can be increased to 1 m if the load connected to switchboard are of category 3 or 4 as per below table.
SPD - Overvoltage category
4. BlokSeT frame of the cubicle or other metallic parts can also be considered as earthing point for SPD, because all the metallic parts in the cubicles has earth continuity.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
유용한 문서
자세히 알아보기
제품군