{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
FAQ 검색
PME - "The HTTP request is unauthorized" error when opening application on Engineering Client
Product Line
Power Monitoring Expert 2020
Power Monitoring Expert 9.0

_____________________________________________________________
Environment
Engineering Client - Applications Login
_____________________________________________________________
Issue
When trying to access any PME applications on the Engineering Client-server, an error message appears:
"The HTTP request is unauthorized with the client authentication scheme 'Negotiate'. The authentication header received from the server was 'Negotiate'."


image.png
_____________________________________________________________
Root Cause
The passwords for the local built-in administrator on the application and client machine are DIFFERENT.
_____________________________________________________________
Proposed Solution
The issue can be avoided by logging into the client machine with a domain account or making sure the local account used exists on both machines with the same password.

슈나이더 일렉트릭 Korea