FAQ 검색
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
Issue
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
Product Line
PO2021
Environment
PSO/PO using Profile Studio to create Equipment package
Solution
There are two ways to solve this....
PO2021 Profile Studio equipment CSV import cause Standby IO Server doesn't exist error
Product Line
PO2021
Environment
PSO/PO using Profile Studio to create Equipment package
Solution
There are two ways to solve this....
- Delete the content of Standby IO Server Name column or configure correct IO Server name in equipment.csv file. and save it.
- Make sure the package received from EPAS-E contains only one OIS HMI and not multiple HMI as below.
게시 대상:슈나이더 일렉트릭 Korea
자세히 알아보기
제품군
자세히 알아보기
제품군