TeSys Giga have different variants of AC/DC wide band control voltage depending on the contactor type. The pick-up and drop-off voltage values are as below:
Note that LC1G630…800 will launch in Q1 2022
Advanced version | Operational limits | |
Pick-up | Drop-off | |
24…48V AC/DC 48…130V AC/DC 200…500V AC/DC | 0.8…1.1 Uc | ≤ 0.45 Uc |
Standard version | ||
48…130V AC/DC 100…250V AC/DC |
Note that LC1G630…800 will launch in Q1 2022
게시 대상:슈나이더 일렉트릭 Korea
TeSys Giga have different variants of AC/DC wide band control voltage depending on the contactor type. The pick-up and drop-off voltage values are as below:
Note that LC1G630…800 will launch in Q1 2022
Advanced version | Operational limits | |
Pick-up | Drop-off | |
24…48V AC/DC 48…130V AC/DC 200…500V AC/DC | 0.8…1.1 Uc | ≤ 0.45 Uc |
Standard version | ||
48…130V AC/DC 100…250V AC/DC |