{}

브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
오늘 무엇을 도와드릴까요?
How to establish the communication with S7-1500 PLC if using TIA Portal Ethernet Driver?

Article available in these languages: 일본어

In PLC side:

1.Use TIA Portal V11-V16 to configure the PLC communication settings.

2.Select the PLC and enter the correct version of the firmware (We can check for the firmware version of the PLC in online mode).

3.Check the PLC firmware version in online mode, make sure the firmware version is supported by TIA Portal V11-V16.

If the firmware version is not supported by TIA Portal V11-V16, communication may not be possible.

If that happens, change the firmware to a version supported by TIA Portal V11-V16 .

In EOTE side:

1.Add TIA Portal Ethernet driver in EOTE.

2.Linking TIA Portal symbols(.ap**) into the EOTE project.

If there are changes to symbols in TIA Portal, linking the new PLC project file(.ap**) into the EOTE project again.

슈나이더 일렉트릭 Korea

Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.