Video: How to sync time between a Machine Expert (EME) PLC and a Operator Terminal Expert (EOTE) HMI?


Issue:
Read the time information from the M241/M251/M262 PLC to synchronize the HMIST6 internal clock.

Product Line:
EcoStruxure Operator Terminal Expert, EcoStruxure Machine Expert

Resolution:
In order to synchronize the HMI time with the PLC time, you must make use of a few libraries in Machine Expert.

You will need to use the following:
SysTimeRtcGet -> This gets the controller's time
SysTimeRtcConvertUtcToDate -> This will convert the controller's UTC info to a readable date
SYSTIMEDATE -> This will store all the date and time information in tags that can be used by the HMI in Operator Terminal Expert.

For a complete setup of an example of how to get and set the PLC time, please see the example in the attached file.
Please download the project to an HMI to test it out. It does not work in simulation mode.

슈나이더 일렉트릭 Korea

첨부 파일
M251_HMIST6_RTC_synchronization.zip [5.83 MB]
Video: How to sync time between a Machine Expert (EME) PLC and a Operator Terminal Expert (EOTE) HMI?


Issue:
Read the time information from the M241/M251/M262 PLC to synchronize the HMIST6 internal clock.
 
Product Line:
EcoStruxure Operator Terminal Expert, EcoStruxure Machine Expert
 
Resolution:
In order to synchronize the HMI time with the PLC time, you must make use of a few libraries in Machine Expert.
 
You will need to use the following:
SysTimeRtcGet -> This gets the controller's time
SysTimeRtcConvertUtcToDate -> This will convert the controller's UTC info to a readable date
SYSTIMEDATE -> This will store all the date and time information in tags that can be used by the HMI in Operator Terminal Expert.
 
For a complete setup of an example of how to get and set the PLC time, please see the example in the attached file.
Please download the project to an HMI to test it out. It does not work in simulation mode.

 
 
 

슈나이더 일렉트릭 Korea

첨부 파일
M251_HMIST6_RTC_synchronization.zip [5.83 MB]
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.