Why the HMI variable parameter of the eCRA device_ddt on M580 HSBY is getting selected automatically at a build ?
Context:
On a control expert project setting with "Embedded data" for datadic with "HMI Only" enable,
When a ECRAis created, the option “HMI Variable” is selected on the device_ddt properties automatically. If this option is unselected, during a build, this option is reselected automatically.
Some customer doesn't want to have those variables inside the datadic.
device ddt ecra

To not have this “HMI variable” selected, the following step need to be follow before performing a build :
workaround

슈나이더 일렉트릭 Korea

Why the HMI variable parameter of the eCRA device_ddt on M580 HSBY is getting selected automatically at a build ?
Context:
On a control expert project setting with "Embedded data" for datadic with "HMI Only" enable,
When a ECRAis created, the option “HMI Variable” is selected on the device_ddt properties automatically. If this option is unselected, during a build, this option is reselected automatically.
Some customer doesn't want to have those variables inside the datadic.
device ddt ecra

To not have this “HMI variable” selected, the following step need to be follow before performing a build :
workaround
 

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.