PowerChute will not connect to Nutanix AHV cluster using SSH key authentication
Issue:
PowerChute Network Shutdown will not connect to Nutanix AHV cluster using SSH key authentication. A connection is made when connecting to the AHV cluster using SSH with username and password. But, when connecting using public/private key authentication, the connection fails.

Product:
PowerChute Network Shutdown

Environment:
PowerChute Network Shutdown on Windows configured with Nutanix AHV.

Cause:
SSH authentication failure when key is created using ssh-keygen on Windows.

Solution:
  1. Use puttygen  (part of Putty toolset https://www.puttygen.com/) to create the keys.
  2. Copy the key to .ssh/authorized_keys on each AHV hosts.
  3. Copy the key to key Prism->Settings->Cluster Lockdown.

슈나이더 일렉트릭 Korea

PowerChute will not connect to Nutanix AHV cluster using SSH key authentication
Issue:
PowerChute Network Shutdown will not connect to Nutanix AHV cluster using SSH key authentication. A connection is made when connecting to the AHV cluster using SSH with username and password. But, when connecting using public/private key authentication, the connection fails.

Product:
PowerChute Network Shutdown 

Environment:
PowerChute Network Shutdown on Windows configured with Nutanix AHV.

Cause:
SSH authentication failure when key is created using ssh-keygen on Windows.

Solution:
  1. Use puttygen  (part of Putty toolset https://www.puttygen.com/) to create the keys.
  2. Copy the key to .ssh/authorized_keys on each AHV hosts.
  3. Copy the key to key Prism->Settings->Cluster Lockdown.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
자세히 알아보기
제품군
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.