{}

브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.

FAQ 검색

How to correctly uninstall the Unitelway driver to reinstall it later if DriverManager cannot recognize the TSX C USB 485 cable?

Context
Sometimes it happens that a TSX C USB 485 cable which works very well is not recognized by DriverManager. To adjust, simply proceed as follows:
First of all,Open Windows start menu → Control Panel → Programs and Features → Right click on Unitelway Driver X64 then select Uninstall
After that, please do the following :
  • Change the name of attachment file as Release-PerUserDrivers.ps1.
  • Right click this file and choose ‘Run with PowerShell’ to run this script file.
  • There will be a log file named as ‘Release-PerUserDrivers.log’ on the desktop.
  • There are some words like this in the log as the blow:
Checking registry at HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows\CurrentVersion\Installer\UserData

Unitelway Driver X64 003.023.00000 (14.13) was installed on 2022-08-09 for user xxx\xxxx
would delete Windows Installer registry key S-1-5-21-3548318340-4179135238-1760686114-1002\Products\3D478988BA188274BA5AFB29B8A99636
would delete setup reference file C:\windows\System32\Unitelw.dll, last modified 2019-02-06
  • Remove the registry key: HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows\CurrentVersion\Installer\UserData\ S-1-5-18\Products\3D478988BA188274BA5AFB29B8A99636. In the log, it is another GUID.
  • Delete or rename the file C:\Windows\System32\ Unitelw.dll.
  • Reinstall the Uniteway Driver installer. It will be OK.

Product Line
Premium, TSX C USB 485,

Environment
Windows 10 Pro, DriverManager, Unitelway Driver X64

슈나이더 일렉트릭 Korea

첨부 파일

Release-PerUserDrivers.txtRelease-PerUserDrivers.txt [18.59 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군