{}

Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.

Поиск часто задаваемых вопросов

How does the high head pressure protection feature work on the ACSC?

Issue:
How does the high head pressure protection feature work?

Product line:
ACSC100, ACSC101

Environment:
InRow Cooling

Cause:

Resolution:
The unit targets a refrigerant condensing pressure of 425 psig (29.3 bar) and the condenser fans modulate to maintain this. The high head pressure switch trip limit is 550 psig (37.9 bars). When condensing pressure reaches 520 psig (35.8 bars), the controller slows the evaporator fans down and opens the electronic hot gas bypass valve to reduce condensing pressure.

Schneider Electric Казахстан

Узнайте больше
Линейка:
Узнайте больше
Линейка: